Commercial AC and VRF error codes.

Ductable, cassette, tower and VRV/VRF systems report faults through a wired controller or remote display. These are shared across multiple indoor units on one refrigerant circuit, so one fault can affect a whole floor.

Jump to: Daikin VRV · Mitsubishi Electric · LG Multi V · Toshiba VRF · Hitachi Set Free · Samsung DVM · Panasonic ECOi · Carrier · Voltas Commercial · Blue Star Ductable · Trane · York · Gree GMV · Midea V6

Note on VRF systems: a single VRF fault can be raised by any one of several indoor units sharing an outdoor unit. Always note which indoor unit’s controller first showed the code — it narrows the fault fast.
Safety first: burning smell, sparking, or a tripped breaker means a possible short circuit — cut power at the main board and call an electrician. Suspected gas leakage or refrigerant faults need a certified technician with proper equipment. See the full disclaimer before acting on any code.
Daikin VRV
CodeLikely meaningWhat to check
U4Transmission error between indoor and outdoor unitsCheck shielded control wiring across all connected indoor units.
E3High pressure protection activatedOutdoor coil blocked or airflow restricted around the outdoor unit.
E4Low pressure protection activatedPossible refrigerant shortage — needs gauge check by a technician.
E7Outdoor fan motor errorCheck for obstruction or a failed outdoor fan motor.
L4/L5Outdoor unit inverter compressor overheatCheck outdoor unit ventilation clearance and ambient temperature.
P4Discharge pipe thermistor abnormalitySensor fault at compressor discharge — technician required.
A1Indoor PCB defectUsually requires indoor board replacement.
C4Indoor heat exchanger sensor errorCheck the indoor coil sensor connection.
C9Indoor suction air sensor errorCheck the suction air sensor wiring.
H8Compressor current sensor errorOutdoor unit fault — needs technician diagnosis.
Mitsubishi Electric
CodeLikely meaningWhat to check
P1Indoor intake air sensor errorCheck the intake sensor wiring and connector.
P6Freeze/high-temperature protectionCheck filter cleanliness and refrigerant charge.
U2High discharge temperature / low refrigerantPossible leak — needs technician inspection.
E6/E7Communication error between indoor and outdoor unitCheck the control wiring across the whole line.
F1Outdoor unit phase reversal or open phaseCheck the incoming power supply phasing.
P8Pipe (liquid) temperature sensor errorCheck the liquid pipe sensor connection.
P9Outdoor unit sensor errorCheck outdoor sensor wiring and connectors.
E0Remote controller signal reception errorCheck the remote controller and its wiring.
E9Indoor/outdoor unit communication mismatchCheck control wiring across all connected indoor units.
L3Outdoor unit electrical box high temperatureCheck outdoor unit ventilation and electrical box cooling.
LG Multi V (VRF)
CodeLikely meaningWhat to check
CH 05Communication error between indoor unit and outdoor VRF moduleCheck the communication cable and its shielding across the line.
CH 10Central controller communication errorCheck wiring and address settings at the central controller.
CH 41High pressure protection on outdoor moduleCheck outdoor coil cleanliness and airflow clearance.
CH 43Low pressure protectionPossible refrigerant shortage — needs gauge check.
CH 53Outdoor unit address duplication or setting errorCheck outdoor module address/rotary switch settings.
CH 38High pressure sensor abnormalCheck outdoor coil cleanliness and airflow clearance.
CH 39Low pressure sensor abnormalPossible refrigerant shortage — needs gauge check.
CH 49Outdoor unit fan motor errorCheck for obstruction or motor failure at the outdoor fan.
CH 61Power factor correction (PFC) circuit errorOutdoor PCB fault — needs technician diagnosis.
CH 65Compressor overcurrentCheck outdoor unit load and ventilation clearance.
Toshiba VRF / SMMS
CodeLikely meaningWhat to check
E03Communication error between indoor and outdoor unitInspect the shielded control cable run.
E04Duplicate indoor unit addressCheck indoor unit address settings on the DIP switches.
E16Capacity over — too many indoor units connectedCheck the total connected indoor capacity against the outdoor rating.
F10High pressure protectionOutdoor coil blocked or ambient temperature too high.
F23Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
F29Outdoor unit fan motor errorCheck for obstruction or motor failure at the outdoor fan.
F31Low pressure protectionPossible refrigerant shortage — needs gauge check.
E01Remote controller communication errorCheck the remote controller wiring.
E20Indoor unit fan motor errorCheck for obstruction or a failed indoor fan motor.
H01Compressor overcurrentCheck outdoor unit load and ventilation clearance.
Hitachi Set Free (VRF)
CodeLikely meaningWhat to check
03Communication error between indoor and outdoor unitCheck control wiring and connector crimps.
07Address setting error / duplicationCheck indoor/outdoor unit address switches.
11Indoor unit fan motor errorCheck for obstruction or a failed indoor fan motor.
31High pressure protection activatedClean the outdoor coil and check airflow clearance.
44Low pressure protection activatedPossible refrigerant shortage — needs technician check.
13Drain pump errorCheck the condensate drain for blockage.
23Outdoor ambient sensor errorCheck the outdoor ambient sensor wiring.
35Compressor overcurrentCheck outdoor unit load and ventilation clearance.
41Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
47Power factor correction (PFC) circuit errorOutdoor PCB fault — needs technician diagnosis.
Samsung DVM (VRF)
CodeLikely meaningWhat to check
E101Communication error between indoor and outdoor unitCheck the communication cable across the whole line.
E458Outdoor unit address duplicationCheck outdoor module address settings.
E501High pressure protectionCheck outdoor coil cleanliness and ventilation clearance.
E505Compressor discharge temperature too highPossible low refrigerant charge — needs technician check.
E455Indoor unit address duplicationCheck indoor unit address/DIP switch settings.
E462Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
E468EEPROM (memory) errorOutdoor PCB fault, usually needs board service.
E652Fan motor errorCheck for obstruction or motor failure at the fan.
E661Power factor correction (PFC) circuit errorOutdoor PCB fault — needs technician diagnosis.
E699Gas leak detectionNeeds a technician with gauges — not a DIY fix.
Panasonic ECOi (VRF)
CodeLikely meaningWhat to check
H11Communication error between indoor and outdoor unitCheck the interconnecting control wiring.
F31High pressure protectionCheck outdoor coil airflow and cleanliness.
F41Low pressure protectionPossible refrigerant leak — needs gauge check.
F97Outdoor fan motor errorCheck for obstruction or motor failure at the outdoor fan.
H14Indoor temperature sensor errorCheck the indoor room sensor connector.
F32Low pressure sensor errorCheck the low pressure sensor and wiring.
F49Outdoor unit EEPROM (memory) errorOutdoor PCB fault, usually needs board service.
H15Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
U6Indoor/outdoor capacity mismatchConfirm indoor units match the outdoor module’s rated capacity.
F91Compressor overcurrentCheck outdoor unit load and ventilation clearance.
Carrier (commercial & ductable)
CodeLikely meaningWhat to check
E1Indoor room temperature sensor errorCheck the sensor at the return air intake.
E4Communication error between indoor and outdoor unitInspect the control cable run.
E8Overload / high pressure protectionClean the outdoor condenser coil and check airflow clearance.
PFCompressor protection faultCheck outdoor unit for overheating or electrical fault.
E2Indoor coil sensor errorCheck the indoor coil sensor connection.
E5Outdoor sensor errorCheck outdoor sensor wiring and connectors.
E6Low pressure protectionPossible refrigerant shortage — needs gauge check.
E9Drain pump errorCheck the condensate drain for blockage.
PLPhase loss / phase reversal errorCheck the incoming power supply phasing.
EEEEPROM (memory) errorOutdoor PCB fault, usually needs board service.
Voltas Commercial
CodeLikely meaningWhat to check
F5Communication error between indoor and outdoor unitCheck the connecting control cable and terminals.
F8High pressure / overload protectionClean the outdoor condenser and check airflow clearance.
F9Outdoor fan motor faultCheck for obstruction or motor failure at the outdoor fan.
F1Indoor room temperature sensor errorCheck the sensor at the return air intake.
F2Indoor coil temperature sensor errorCheck the coil sensor clip and wiring.
F6EEPROM (memory) errorOutdoor PCB fault, usually needs board service.
F7Outdoor ambient temperature sensor errorCheck the outdoor ambient sensor connection.
F10Low pressure protectionPossible refrigerant shortage — needs gauge check.
F11Compressor overcurrentCheck outdoor unit load and ventilation clearance.
F12Gas leak detectionNeeds a technician with gauges — not a DIY fix.
Blue Star Ductable / Cassette
CodeLikely meaningWhat to check
E1Room/return air sensor errorCheck the return-air sensor wiring.
E7Outdoor unit communication faultCheck control wiring between the ductable indoor unit and outdoor unit.
P1High pressure protectionClean outdoor coil, check ductwork isn’t overly restrictive.
E2Indoor coil sensor errorCheck the coil sensor clip position.
E3EEPROM (memory) errorIndoor/outdoor PCB fault, usually needs board service.
E4Drain pump / float switch errorCheck the condensate drain line for blockage.
E5Low pressure protectionPossible refrigerant shortage — needs gauge check.
E6Compressor overcurrent protectionCheck outdoor unit load and ventilation clearance.
E8Gas leak detectionNeeds a technician with gauges — not a DIY fix.
E9Outdoor fan motor errorCheck for obstruction or motor failure at the outdoor fan.
Trane (North America)
CodeLikely meaningWhat to check
E1High pressure protectionClean outdoor coil and check airflow clearance.
E2Low pressure protectionPossible refrigerant shortage — needs gauge check.
E3Compressor overcurrentCheck outdoor unit load and ventilation clearance.
E4Communication error between unitsInspect the connecting cable and terminals.
E5Outdoor fan motor errorCheck for obstruction or motor failure.
E6Indoor coil sensor errorCheck the indoor coil sensor connection.
E7Outdoor coil sensor errorCheck the outdoor coil sensor connection.
E8EEPROM (memory) errorPCB fault, usually needs board service.
E9Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
E10Power supply voltage abnormalityCheck incoming voltage and phasing.
York (North America)
CodeLikely meaningWhat to check
P1High pressure protectionClean outdoor coil and check airflow clearance.
P2Low pressure protectionPossible refrigerant shortage — needs gauge check.
P3Compressor overloadCheck outdoor unit ventilation clearance.
E1Communication error between unitsInspect the connecting cable and terminals.
E2Indoor sensor errorCheck the indoor sensor connection.
E3Outdoor sensor errorCheck the outdoor sensor connection.
E4EEPROM (memory) errorPCB fault, usually needs board service.
E5Fan motor errorCheck for obstruction or motor failure.
E6Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
E7Voltage or phase errorCheck incoming power supply phasing.
Gree GMV (global)
CodeLikely meaningWhat to check
E1High pressure protectionClean outdoor coil and check airflow clearance.
E2Low pressure protectionPossible refrigerant shortage — needs gauge check.
E3Compressor overcurrentCheck outdoor unit load and ventilation clearance.
E5Communication error between unitsInspect the connecting cable and terminals.
E6Indoor coil sensor errorCheck the indoor coil sensor connection.
E8Outdoor coil sensor errorCheck the outdoor coil sensor connection.
F0EEPROM (memory) errorPCB fault, usually needs board service.
F1Discharge temperature sensor errorSensor fault at compressor discharge — technician required.
F2Fan motor errorCheck for obstruction or motor failure.
F5Power supply voltage abnormalityCheck incoming voltage and connections.
Midea V6 (global)
CodeLikely meaningWhat to check
E1High pressure protectionClean outdoor coil and check airflow clearance.
E2Low pressure protectionPossible refrigerant shortage — needs gauge check.
E3Compressor overloadCheck outdoor unit ventilation clearance.
E4Communication error between unitsInspect the connecting cable and terminals.
E5Indoor sensor errorCheck the indoor sensor connection.
E6Outdoor sensor errorCheck the outdoor sensor connection.
E8EEPROM (memory) errorPCB fault, usually needs board service.
P0Discharge temperature protectionSensor fault at compressor discharge — technician required.
P1Fan motor errorCheck for obstruction or motor failure.
P2Voltage or phase errorCheck incoming power supply phasing.
Advertisement space

Looking for a home split or window unit instead? See split AC codes or window AC codes.